During recent industry show inspections, Caravan Industry Association of Australia’s RVMAP Team observed several instances where electrical outlets and switches were installed within the exclusion zone around damp areas, such as around showers, sinks and basins.
These locations present an increased safety risk if equipment is not installed in accordance with the relevant Australian Standards.
The placement of electrical equipment in these areas is covered under AS/NZS 3001.2:2022 – Electrical installations – Connectable electrical installations and supply arrangements; Part 2: Connectable electrical installations.
The standard specifies strict requirements for:
Incorrect placement of electrical devices within these areas can result in non-compliance and pose serious safety risks.
For detailed zone diagrams, installation requirements and guidance on compliant equipment, visit the RV Electrical Ready website.
Any questions can be emailed to [email protected]
